MEDICAL
AIR TREATMENT SYSTEM WITH
REFRIGERATED AIR DRYERS
Furnish and install, where shown on the drawings a prefabricated Medical Air Treatment system with refrigerated air dryers model 3DRZ______ as manufactured by:
Amico Source
Toll Free Tel: 1.877.462.6426
The unit furnished shall be a standard
catalog item of the supplier regularly engaged in the business of providing
packaged systems for hospitals and laboratories and shall meet and exceed the
requirements of NFPA 99.
The Amico Alert-2 Duplex Refrigerated
Air Dryer system shall be a completely packaged NFPA 99 and NEC compliant
assembly featuring dual refrigerated air dryers, dual 0.5 micron after-filters,
line pressure regulating valves, dew point monitor, CO monitor and other
accessories required to meet and exceed the current code requirements. All
components are pre-piped and pre-wired to single-point service connections. The
only field connections are air intake, air discharge and the power connection.
All interconnecting copper/brass piping as well as wiring is completed and
operationally tested prior to shipment.
Each unit consists of two identical
banks of air treatment equipment, piped in parallel and provided with valves to
by-pass either filter set for element replacement, maintenance and repair work
on one of the sets while still treating medical compressed air through the other
set without any sacrifice in air quality.
Refrigerated self-contained cycling air
dryers (designed to successfully operate at low load or no load conditions)
utilize the minimum refrigerant charge for maximum environmental safety. No CFCs
used. Maintenance-free high efficiency refrigerant compressors are standard.
Moisture separator with automatic drain remove moisture down to +35oF
pressure dew point. The dryers shall be equipped with electronic dew point
temperature display and built-in electronic drain.
0.5 micron after-filters are prime
efficiency coalescers with particle removal down to 0.5 micron.
Downstream pressure regulators maintain constant discharge pressure of 55 PSIG (field adjustable).
Digital dew point and CO monitors with
alarm set points at 390F
and 10 PPM are provided with dry contacts for connection to remote alarm panels.
A "demand check" for maintenance is included per current NFPA 99 for
each instrument.
The Medical Air Treatment system is
guaranteed in writing by the
manufacturer for a period of 12 months from the date of start-up or 18 months
from the date of shipment (whichever comes first) against defects in design,
materials, or construction.
The service of a factory trained
representative will be available at
the jobsite to check installation,
start-up and instruct operating personnel in proper operation and maintenance.